WALKED Sample Inspections
Front of the house
Sample reportReal photo, location and owner removed.

Sample town · Sample county · Ohio

See what a WALKED report looks like.

Inspection day · 10:00 AM · Clear
Single-family brick ranch · attached one-car garage · Vacant · not occupied
WALKED Sample Inspector · Ohio HI OHI.0000000 (sample) · (555) 010-0100

6Hire a Pro
1DIY
7Noted

Big ones first: cracked brick and broken mortar at the chimney top; open splices in the basement ceiling; galvanized steel water pipe, rusted at the fittings; damaged shingle — lifted and creased; trees growing against the roof edge; and plumbing vent pipe rusted, boot patched with tar. The attic was viewed from the access opening only. DIY is dryer vent hood packed with lint.

Every fix is Hire a Pro or DIY. Noted is age, monitor, limits, info. Not a seller punch list.

Fix these before you close

Hire a Pro

Chimney top: cracked brick and broken mortar

Chimney top: cracked brick and broken mortar

At the top of the chimney, the mortar has broken out of the top courses and some bricks are cracked.

Chimney, top courses
Hire a Pro

Water that gets in here works down into the chimney.

Hire a mason or chimney contractor to rebuild the top courses and the crown.

Open splices hanging below an uncovered junction box

Open splices hanging below an uncovered junction box

A metal junction box in the basement ceiling has no cover. The splices sit outside the box, with the wire nuts hanging in the open below the joists.

Basement ceiling, beside the main duct
Hire a Pro

Splices belong inside a covered box so a loose connection can't touch wood or a hand.

Hire a licensed electrician. Put the splices inside a box, install the cover, and secure the cable.

Galvanized steel water pipe, rusted at the fittings

Galvanized steel water pipe, rusted at the fittings

Part of the water supply is galvanized steel. The fittings are rusted and swollen, with copper spliced in at some joints.

Basement ceiling, supply lines
Hire a Pro

Galvanized pipe rusts from the inside, which cuts water flow. The rusted fittings are where leaks start.

Hire a licensed plumber to replace the galvanized supply piping.

Damaged shingle: lifted and creased

Damaged shingle: lifted and creased

One shingle is lifted and creased across the tab, so it no longer lies flat.

Roof, main slope
Hire a Pro

A creased tab lets wind and water get under it, and the next storm can tear it off.

Hire a licensed roofer to replace the damaged shingle and check the rest of the slope.

Trees growing against the roof edge

Trees growing against the roof edge

Tree trunks and limbs rest on the roof edge and lie across the shingles.

Rear roof edge
Hire a Pro

Limbs scrape off granules, hold debris and moisture on the roof, and give animals a path in.

Hire a tree service to cut the limbs well back from the roof, then have a roofer check the shingles underneath.

Plumbing vent pipe rusted, boot patched with tar

Plumbing vent pipe rusted, boot patched with tar

The metal plumbing vent pipe is rusted through its surface, and the flashing boot around it is smeared with tar that has cracked.

Roof, plumbing vent
Hire a Pro

Rust and failed tar at a roof penetration let water into the attic.

Hire a roofer, with a plumber if the pipe needs a new section, to replace the vent pipe stub and install a new boot.

You can handle these

DIY

Dryer vent hood packed with lint

Dryer vent hood packed with lint

The outside dryer vent hood is stuffed with lint, and the flap can't open.

Exterior, laundry wall
DIY!

A blocked dryer vent is a fire risk and makes the dryer run longer.

DIY: pull the lint out of the hood by hand, then run a dryer-vent brush kit (hardware store) through the duct. Clean the lint screen every load.

The machines

Nameplates & ages.

The big machines · how old is this stuff?

The big machines · how old is this stuff?

Most of the big gear here is past its first decade. Plates and labels below; each age says where it came from.

Gear
Plates read
Furnace
Gas furnace · heats the house
Serial decode dates it to 2008 (unverified decode)

Heats the house.

Ducane
Air conditioner
Outdoor AC · model code suggests about 3 tons (unverified)
Built July 2008 (per the data plate)

Cools the house.

Trane
Water heater
Gas tank · 40 gallons
Built March 2010 (per the data plate)

Hot water for the house. Rusted supply pipe is a separate Hire a Pro.

Richmond
Main electric panel
100-amp main breaker
No date on the label · age not determined

Feeds every circuit in the house. Open wiring is a separate Hire a Pro.

Square D Homeline
Water main
Water meter with the main shutoff valve beside it
No data plate

Shown so you can find the shutoff.

Gas meter
Gas service at the meter
No data plate

Shown so you can find the meter shutoff.

Nameplate inventory only. Not a warranty claim and not a promise of remaining life.

Furnace · Gas furnace

Furnace · Gas furnace

Gas furnace, direct vent, forced air. Make: Ducane (Allied Air Enterprises). Model: CMPE050U3B. Serial: 4045430•••. Size: 50,000 BTU per hour input (plate).

Heat
2008

About 0 to 7 years left on a typical 15 to 25 year range.

Noted. Serial decode dates it to 2008 (unverified decode). About 18 years old.

Air conditioner · Outdoor AC

Air conditioner · Outdoor AC

Central air conditioner, outdoor condensing unit. Make: Trane. Model: 4TTX5036A1000AA (XL15i). Serial: 8294WP•••. Size: model code suggests 3 tons (unverified); plate: MCA 22.0 A (the smallest wire size the circuit needs), max breaker 35 A.

Cooling
2008

Past the typical 7 to 15 year range.

Noted. Built July 2008 per the data plate. About 18 years old.

Water heater · Gas tank

Water heater · Gas tank

Tank water heater, atmospheric vent. Make: Richmond (Rheem Manufacturing Co.). Model: 6G40-36F1. Serial: RMLN0310412•••. Size: 40 gallons; 36,000 BTU per hour input (plate).

Water
2010

Past the typical 6 to 12 year range.

Noted. Built March 2010 per the data plate. About 16 years old. Rusted supply pipe is a separate Hire a Pro.

Main electric panel · 100-amp main breaker

Main electric panel · 100-amp main breaker

Main breaker panel, circuit breakers. Make: Square D Homeline. Model: HOMC21UC (door label). Serial: none on the label. Main breaker handle reads 100 amps.

Power
Age not determined

Noted. No manufacture date on the label in these photos, so age is not determined. Open wiring is a separate Hire a Pro.

Systems at a glance

Roof

Covering Material: Asphalt shingles · Roof Age: Not estimated. No photo in this set shows a dated label, permit or receipt, and worn granules alone do not date a roof. Ask the seller for the roofing invoice · Inspection Method: Viewed from the roof edge and the ground

Coverage: viewed from the roof edge and the ground. The back slope behind the ridge was not fully visible.

Exterior

Wall Covering Material: Brick on the front (cover photo); vinyl siding on the walls in the finding photos

Structure / foundation

Foundation Type: Basement · Floor Structure: Not verified. Floor framing is not in the walk photos, and hidden conditions behind finishes are outside this visual walk · Wall Structure: Concealed by finishes · Ceiling Structure: Concealed by finishes · Roof Structure: Wood rafters and sheathing

Coverage: basement walls where not covered by finishes or storage.

Heating

Energy Source: Natural gas · Method Or System Type: Gas furnace, direct vent, forced air · Thermostat Location: Not inspected: no photo of the thermostat in this composite sample, so its location is not recorded. · Approximate Age: Data plate dates it to 2008.

Cooling

Energy Source: Electric, 208/230 V, 1 phase · Method Or System Type: Central air conditioner, outdoor condensing unit · Approximate Age: Data plate dates it to 2008.

Plumbing

Water Supply Public Or Private: Public: water meter at the main (photo under Data plates and ages) · Supply Piping Materials: Copper and galvanized steel · Drain, waste, vent Piping Materials: Not inspected: no photo of the interior drain, waste and vent piping in this composite sample, so its material is not recorded. Buried drain lines are outside a visual walk. · Main Water Shutoff Location: Valve beside the water meter (photo) · Main Fuel Shutoff Location: At the gas meter (photo). Interior shut-off: not inspected; not in the photo set for this composite sample

Water heater

Energy Source: Natural gas · Type: Tank water heater, atmospheric vent · Approximate Age: Data plate dates it to 2010.

Electrical

Service Amperage: 100-amp main breaker (handle reads 100) · Main Disconnect Location: Main breaker in the main panel (handle reads 100 amps) · Subpanel Locations: None seen · Branch Wiring Method: NM cable (plastic-sheathed cable) · Smoke Alarms Presence: Present on the hall ceiling (photo above). Alarms were not tested · CO Alarms Presence: Not inspected: no carbon monoxide (CO) alarm photo in this composite sample, so presence or absence is not recorded. Confirm a working CO alarm on every level before move-in.

Fireplace / fuel-burning

Type: Masonry chimney; flue interior not inspected

Attic, insulation, ventilation

Attic Inspection Method: Viewed from the attic access · Insulation Type: Loose fill · Approximate Depth Attic: Not inspected: depth was not measured in the photo set for this composite sample · Ventilation Type: Not inspected: attic vents are not in the photo set for this composite sample

Coverage: viewed from the access opening only. Areas past the insulation and down at the eaves were not visible. Percent of attic viewed was not recorded for this sample.

Interior, doors, windows

Method: Representative doors and windows operated

Garage

Door Operation: Not tested. Check that the door reverses when something blocks it

Kitchen appliances

Primary List: Not inspected: kitchen appliances were not in the photo set for this composite sample.

Age, settlement & leftovers

Just so you know.

Smoke alarm present in the hall

Smoke alarm present in the hall

A smoke alarm is mounted on the hall ceiling. It was not push-tested.

Hall ceiling
Noted

Noted. Test it when you move in.

House age · ask for paperwork

Plenty of original parts in a house this age. Ask the seller for receipts, permits and service records for the roof, furnace, AC and water heater.

Paperwork
Ask seller

Noted. This is a due-diligence ask, not a code finding.

It’s not too late

Book these before you close.

Sewer scope

A camera look is the only way to see roots, breaks or sags in the buried drain line.

Text WALKEDCall

Radon test

Radon can’t be seen or smelled. A short test gives you the number.

Text WALKEDCall

Chimney flue inspection (Level II)

The inside of the flue was not inspected. A chimney sweep can camera it before the first fire.

Text WALKEDCall

Lab tests, radon and pest inspections are separate from the visual walk.

Not this walk

Didn’t open it. Here’s why.

Roof install date. No permit or date to verify, so roof age is not estimated.

Attic beyond the access opening. Viewed from the opening only. The share of the attic seen was not recorded for this sample, and the eaves were not visible.

Chimney flue interior / Level II. Not a chimney safety inspection.

Heat exchanger interior. Stays closed. Visual furnace only.

Air conditioner output. Plate documented under the machines. Cooling output was not measured.

Water heater pressure-relief pipe. This pipe (the TPR, or temperature and pressure relief, discharge pipe) carries scalding water away if the tank overheats. Where it ends was not traced. A plumber can confirm it is routed safely.

Kitchen and bath outlets. A GFCI (a shock-protection outlet with Test and Reset buttons that cuts power fast if current leaks through water or a person) protects wet areas. These were not tested. Press Test, then Reset, on each one after you move in.

Smoke and carbon monoxide alarms. A smoke alarm is present on the hall ceiling. Alarms were not tested. no carbon monoxide (CO) alarm photo in this composite sample, so presence or absence is not recorded. Confirm a working CO alarm on every level before move-in.

Wall insulation. Finished walls hide it, so the amount of insulation, or whether there is any, is unknown.

Buried water, gas and sewer lines. Not visible. Underground pipes are not dug up on a visual walk. See sewer scope above.

Termites and other wood-eating insects. A full pest inspection was not part of this walk.

Garage door auto-reverse and photo-eye safety. Not tested on this walk. Check that the door reverses when something blocks it.

Behind finishes, furniture and storage. Not moved or opened. Concealed conditions are outside a visual walk.

Thermostat. no photo of the thermostat in this composite sample, so its location is not recorded.

Interior drain, waste and vent piping. no photo of the interior drain, waste and vent piping in this composite sample, so its material is not recorded. Buried drain lines are outside a visual walk.

Kitchen appliances. kitchen appliances were not in the photo set for this composite sample.

Photo appendix

Additional photos from the walk.

Extra frames that support the findings above. Duplicates and throwaway shots were pulled.

Equipment schedule · Furnace data plate
Equipment schedule · Furnace data plate
Equipment schedule · Air conditioner data plate
Equipment schedule · Air conditioner data plate
Equipment schedule · Water heater data plate
Equipment schedule · Water heater data plate
Main electric panel, cover off
Main electric panel, cover off
Equipment schedule · Main electric panel data plate
Equipment schedule · Main electric panel data plate
Water main and shutoff
Water main and shutoff
Gas meter
Gas meter

Ohio law · plain English

Standards of practice — what this report is (and isn’t)

A visual inspection of readily accessible systems and parts, as they looked on inspection day. Not a code inspection, appraisal, warranty or engineering study.

Ohio home inspections follow Ohio Revised Code Chapter 4764 and the Ohio Home Inspector Board rules (OAC 1301:17-1-16 and 1301:17-1-17).

What this inspection covers

What it does not cover

Not covered: radon, mold lab testing, asbestos, lead paint, water chemistry, wood-destroying insects, buried tanks, wells, septic systems and underground piping.

Limits on this walk

Read the official rules:

Inspector attestation

Signed.

Redacted for privacy

WALKED Sample Inspector · WALKED Sample Inspections
Ohio HI OHI.0000000 (sample)

Sample report built from more than one inspection. Real photo, location and owner removed. A visual inspection of readily accessible systems and parts, as they looked on inspection day. Not a code inspection, appraisal, warranty or engineering study. Hidden conditions behind finishes, buried piping, radon, lab testing, wood-destroying insects and water chemistry are outside a visual walk unless ordered separately.